- Operating temperature: Max.Permissible continuous operating temperature of Conductors shall not exceed 90¡æ?/li>
|
- Conductor Short circuit temperature: No exceeding 250¡æ?Max.Sustaining period:
No exceeding 5 seconds.
|
- Bending radius:
Bending radius of single core cable:20D
Bending radius multi-core cable:15D
D=Actual overall diameter of cable sample(mm)
|
- Installation temperature:
The lowest temperature of installation is 0¡æ?
Current ratings and basic parameters are calculated under the following cable laying conditions and basic ambient temperature.
Layout of single core cables:In parallel
(Spacing side by side:1D D = overall diameter)
method of laying |
Basic ambient temperature |
In air |
40¡æ?/div> |
Directburial |
25¡æ?/div> |
|
Soil thermal resistivity 1.0K*m/V |
|
1 Conductor
|
2 Conductor Screen |
3 XLPE Insulation |
4 Insulation |
5 Metallic Screen |
6 Fille |
7 Sperating Sheath (Inner Covering) |
8 Armour |
9 Oversheath |
|
Note: For cables Uo lower than 3.6KV , No conductor screen and insulation screen are appulied. |
| TYPE |
No.Of cores |
Rated coltange(kv) |
06/1 |
1.8/3 |
3.6/6 |
6/6 6/10 |
8.7/10 8.7/15 |
| Nominal area of conuctor (mm2) |
YJV
YJLV
YJV22
YJLV22
YJV32
YJLV32 |
1,2,3
3+1, 3+2
4+1, 5 |
1.5-400 |
10-400 |
25-400 |
25-400 |
25-400 |
| 1.5-300 |
- |
- |
- |
- |
| 1.5-300 |
10-300 |
25-300 |
25300 |
25-300 |
| 1.5-300 |
- |
- |
- |
- |
| 1.5-300 |
- |
- |
- |
- |
| 4-300 |
- |
- |
- |
- |
| 4-300 |
10-300 |
25-300 |
25-300 |
25-300 |
| 4-300 |
- |
- |
- |
- |
| 4-300 |
- |
- |
- |
- |
| 10-300 |
- |
25-300 |
25-300 |
25-300 |
| 4-300 |
- |
25-300 |
25-300 |
25-300 |
| 2.5-300 |
- |
- |
- |
- |
| 2.5-300 |
- |
- |
- |
- |
| 2.5-300 |
- |
- |
- |
- |
TYPE |
Description
|
Main Application |
YJV
YJLV |
Cu or Al conductor XLPE insulated PVC Sheath
|
For laying indoor and outdoor,unable to bear extermal mechanical force but the tractive force during laying.
Laying Single cable in magnetic is not permissble |
YJV22
YJLV22 |
Cu or Al conductor XLPE insulated steel tape armored PVC Sheath |
For laying underground ,able to bear external mechanical force, but unable to bear large pulling force |
YJV32
YJLV32 |
Cu or Al conductor XLPE insulated thin tape wire armored PVC Sheathed power cable |
For laying underground ,vertical well,or underwater,able to bear certain pulling force. |