www.ghcable.comABC cable, ACSR Conductor, Wilding Cable, ACSR cable, AAAC cable, Single wire, Rubber Cable, Control Cable, Speaker Wire, POWER CABLE]

 

 

 

   
6
Power Cable
6.1
XLPE insulated power cable
6.1.1
XLPE insulated power cable with rated coltage 1kV(Um=1.2kV) & 35kv(Um=40.5kV)
POWER Cable wwwo.ghcable.com

a

Service performance

 

  • Operating temperature: Max.Permissible continuous operating temperature of Conductors shall not exceed 90¡æ?/li>
  • Conductor Short circuit temperature: No exceeding 250¡æ?Max.Sustaining period: No exceeding 5 seconds.
  • Bending radius:
    Bending radius of single core cable:20D
    Bending radius multi-core cable:15D
    D=Actual overall diameter of cable sample(mm)
  • Installation temperature:
    The lowest temperature of installation is 0¡æ?
    Current ratings and basic parameters are calculated under the following cable laying conditions and basic ambient temperature.
    Layout of single core cables:In parallel (Spacing side by side:1D D = overall diameter)
method of laying
Basic ambient temperature
In air
40¡æ?/div>
Directburial
25¡æ?/div>
Soil thermal resistivity 1.0K*m/V

b

Structure

XLPE insulated power cable with rated coltage 1kV www.ghcable.com
XLPE insulated power cable with rated coltage 1kV www.ghcable.com XLPE insulated power cable with rated coltage 1kV www.ghcable.com
Single-core nonarmoured
YJV YJLV
Three-core steel tape armoured
YJV YJLV
Three-core steel tape armoured
YJV YJLV
1 Conductor
2 Conductor Screen
3 XLPE Insulation
4 Insulation
5 Metallic Screen
6 Fille
7 Sperating Sheath (Inner Covering)
8 Armour
9 Oversheath
 
Note: For cables Uo lower than 3.6KV , No conductor screen and insulation screen are appulied.

c

Scope of cable
TYPE No.Of cores Rated coltange(kv)
06/1
1.8/3
3.6/6
6/6
6/10
8.7/10
8.7/15
Nominal area of conuctor (mm2)
YJV
YJLV
YJV22
YJLV22
YJV32
YJLV32
1,2,3
3+1, 3+2
4+1, 5
1.5-400 10-400 25-400 25-400 25-400
1.5-300 - - - -
1.5-300 10-300 25-300 25300 25-300
1.5-300 - - - -
1.5-300 - - - -
4-300 - - - -
4-300 10-300 25-300 25-300 25-300
4-300 - - - -
4-300 - - - -
10-300 - 25-300 25-300 25-300
4-300 - 25-300 25-300 25-300
2.5-300 - - - -
2.5-300 - - - -
2.5-300 - - - -

d

Type & description

TYPE

Description
Main Application
YJV
YJLV

Cu or Al conductor XLPE insulated PVC Sheath

For laying indoor and outdoor,unable to bear extermal mechanical force but the tractive force during laying.
Laying Single cable in magnetic is not permissble
YJV22
YJLV22
Cu or Al conductor XLPE insulated steel tape armored PVC Sheath For laying underground ,able to bear external mechanical force, but unable to bear large pulling force
YJV32
YJLV32
Cu or Al conductor XLPE insulated thin tape wire armored PVC Sheathed power cable For laying underground ,vertical well,or underwater,able to bear certain pulling force.
Copyright: GHCABLE(Danyang Ganghong Electric Wire & Power Cable Co., Ltd)