XLPE insulated pwoer cable
6.1.2
XLPE insulated power cable with rated coltage from 3.6/6kv to 26/35kv
POWER Cable wwwo.ghcable.com

a

Standard

 

  • XLPE insulated pwoer cable with rated coltage from 3.6/6kV to 26/35kV is produced according to Manufactorer Standard Q/320481LL019-2003(The main quality and specification are higher than IEC60502-1998, IEC60840-1998, GB/T12706-2002.

b

Application

  • Maximum rated operation temperature of conductor:90¡æ?br />
  • Maximum short circuit temperature of conductor (duration 5sec.)250¡æ?/li>
  • It should be pre-warmed before installation when the ambient temperature is below 0¡æ?
  • Minimum bending radius of cable for installation(D is the overall diameter of cable):
    For non-armoured single core cable:20D
    For non-armoured three-core cable:15D
    For armoured single core cable:15D
    For armoured three-core cable:12D

c

Structure

XLPE insulated power cable with rated coltage from 3.6_6kv to 26_35kv www.ghcable.com

XLPE insulated power cable with rated coltage from 3.6_6kv to 26_35kv www.ghcable.com XLPE insulated power cable with rated coltage from 3.6_6kv to 26_35kv www.ghcable.com

d

Conteast Table of Main technical properties among different standards
Items Q/320481LL019-2003
(Enterprise Standard)
IEC60502-1998
IEC60840-1999
GB/T12706-2002
Routine Partial discharge test Discharge magnitude at 2Uo shall not exceed 5PC. For cable of Uo�8kv ,discharge magnit-ude at 1.73Uo shall not exceed 10PC; For cable of Uo>18kv ,discharge magnitude at 1.73Uo shall not exceed 10PC. Discharge magmitude at 1.73Uo shall not exceed 10PC.
Routine A.C.voltage text For cable of Uoâ‰?8kv,test voltage of 3.5Uo shall be app-lied for 5 minutes and no brea-kdown of insulation shall occcur; For cable of Uoâ‰?8kv,test voltage of 3.5Uo shall be app-lied for 5 minutes and no brea-kdown of insulation shall occcur; For calbe of Uo â‰?8kv,test For cable of Uo¡Ü18kv,test voltage of 3.5Uo shall be app-lied for 5 minutes and no brea-kdown of insulation shall occcur;
  For cable of Uoâ‰?8kv.test voltage of 3.5Uo shall be applied for 5 minutes of 2.5Uo shall be applied for 5 minutes. no breakdown of insulation shall occur. For cable of Uo>18kv.test voltage of 2.5Uo shall be applied for 30 minutes no breakdown of insulation shall occur. For cable of Uo¡Ü18kv.test voltage of 3.5Uo shall be applied for 5 minutes of 2.5Uo shall be applied for 5 minutes. no breakdown of insulation shall occur.
Insulation shrinkage test Not more than 2% Not more than 4% Not more than 4%
Hot set test Not more than 130% Not more than 175% Not more than 175%
Measurement on cores at the maxi-mum temperature of calbe For cable of Uoâ‰?kv and Uo â‰?8kv; not more than 40*10; For cable of Uo>18kv; not more than 5*10 For cable of Uoâ‰?kv and Uo â‰?8kv; not more than 80*10; For cable of Uo>18kv; not more than 10*10 For cable of Uo¡Ý6kv and Uo ¡Ü18kv; not more than 80*10; For cable of Uo>18kv; not more than 10*10
Insulation eccentricity(2) Not more than 8%    
Conductor compacted factor Not less than 90%    

Note:

  1. Insulation calculating formular: P=(Smax-Smin)/Smax
  2. P-Insulation eccentriity Smax-Max.insulation thickness of the same section; Smin -Min.insulation thickness of the same section.

e

Type & description
Type Description Installation location
Coper core Aluminium core
YJV YJLV XPLE insulated PVC sheathed power cable Aerial, indoor, trench,
channel and conduit
YJY YJLY XPLE insulated PVC sheathed power cable Aerial, indoor, trench,
channel and conduit
YJV22 YJLV22 XPLE insulated steel tape armoured and PVC sheathed power cable Aerial,trench,
channel and conduit
YJV23 YJLV23 XPLE insulated steel tape armoured and PE sheathed power cable Aerial,trench,
channel and conduit
YJV32 YJLV32 XPLE insulated fine steel wire armoured and PVC sheathed power cable Large difference shaft and underwater
YJV33 YJLV33 XPLE insulated fine steel wire armoured and PE sheathed power cable Large difference shaft and underwater
YJV42 YJLV42 XPLE insulated thick steel wire armoured and PVC sheathed power cable The shaft for bearing large
YJV43 YJLV43 XPLE insulated thick steel wire armoured and PE sheathed pwoer cable
puling force and submarine

f

Rated voltage of cable,nominal sectional area and no.of core
Type No.of
Core
Rated Voltage(kv)
12/20 18/30-26/35
Nominal cross sectional area(mm?
YJV YJLV 1 25-1200 35-1200
YJY YJLY 25-1200 35-1200
YJV32 YJLV32 25-1200 35-1200
YJV33 YJLV33 25-1200 35-1200
YJV42 YJLV42 25-1200 35-1200
YJV43 YJLV43 25-1200 35-1200
YJV YJLV 3 25-500 35-500
YJY YJLY 25-500 35-500
YJV22 YJLV22 25-500 35-500
YJV23 YJLV23 25-500 35-500
YJV32 YJLV32 25-500 35-500
YJV33 YJLV33 25-500 35-500
YJV42 YJLV42 25-500 35-500
YJV43 YJLV43 25-500 35500