Jiangsu Ganghong Electric Wire and Power Cable Corporation Limited

,

AAC- All Aluminum Stranded Conductors (DIN 48201-5)

AAC- All Aluminum Stranded Conductors (DIN 48201-5)

Application

It is mainly used for overhead power transmission lines.

Standards

DIN 48201-5: Aluminum Strandedd Conductors

Construction: Aluminum 1350-H19 wires, concentrically stranded

Technical Parameter

Area Stranding and Wire Diameter  Overall Diameter Linear Mass Calculated Breaking Load Maximum DC Resistance  at 20℃
Nominal  (mm2) Actual (mm2) mm mm kg/km KN Ω/km
16 15.89 7/1.71 5.1 44 2.9 1.8018
25 24.25 7/2.10 6.3 67 425.0 1.1808
35 34.36 7/2.50 7.5 94 5.9 0.8332
50 49.48 7/3.00 9.0 135 8.1 0.5786
50 48.36 19/1.80 9.0 133 8.6 0.595
70 65.82 19/2.10 10.5 181 11.5 0.4371
95 93.27 19/2.50 12.5 256 16.0 0.3084
120 117 19/2.80 14.0 322 19.1 0.2459
150 147.1 37/2.25 15.2 406 25.7 0.196
185 181.6 37/2.50 17.5 501 31.1 0.1587
240 242.54 61/2.25 20.2 670 40.2 0.1191
300 299.43 61/2.50 22.5 827 48.5 0.0965
400 400.14 61/2.89 26.0 1105 61.9 0.07221
500 499.83 61/3.23 29.1 1381 76.0 0.05781
625 626.2 91/2.96 32.6 1733 96.9 0.04625
800 802.1 91/3.35 36.8 2219 120.55 0.03611
1000 999.71 91/3.74 41.1 2766 148.45 0.02897
Scroll to Top