Jiangsu Ganghong Electric Wire and Power Cable Corporation Limited

,

AAC- All Aluminum Stranded Conductors (BS 215-1)

AAC- All Aluminum Stranded Conductors (BS 215-1)

Application

It is mainly used for overhead power transmission lines.

Standards

BS 215-1: Aluminum Strandedd Conductors

Construction: Aluminum 1350-H19 wires, concentrically stranded

Technical Parameter

Code Name Nominal Aluminium Area Stranding and Wire Diameter Sectional Area Overall Diameter Linear Mass Calculated Breaking Load Maximum DC Resistance at 20℃
mm2 mm mm2 mm kg/km kN Ω/km
Midge 22 7/2.06 23.33 6.18 64 3.99 1.227
Aphis 25 3/3.35 26.4 7.2 73 4.11 1.081
Gnat 25 7/2.21 26.8 6.6 73 4.59 1.066
Weevil 30 3/3.66 31.6 7.9 86 4.86 0.9082
Mosquito 35 7/2.59 37 7.9 101 6.03 0.7762
Ladybird 40 7/2.79 42.8 8.4 117 6.87 0.6689
Ant 50 7/3.10 52.83 9.3 145 8.28 0.5419
Fly 60 7/3.40 63.55 10.2 174 9.9 0.4505
Bluebottle 70 7/3.66 73.7 11.0 202 11.34 0.3881
Earwig 75 7/3.78 78.5 11.4 215 11.94 0.3644
Grasshopper 80 7/3.91 84.1 11.7 230 12.78 0.3406
Clegg 90 7/4.17 95.6 12.5 262 14.53 0.2994
Wasp 100 7/4.39 106 13.17 290 16.0 0.2702
Beetle 100 19/2.67 106 13.4 293 17.42 0.2704
Bee 125 7/4.90 132 14.7 361 19.94 0.2169
Cricket 150 7/5.36 157.9 16.1 432 23.85 0.1818
Hornet 150 19/3.25 157.6 16.25 434 25.7 0.1825
Caterpillar 175 19/3.53 186 17.7 512 28.63 0.1547
Chafer 200 19/3.78 213.2 18.9 587 32.4 0.1349
Spider 225 19/3.99 236.9 20.0 652 36.01 0.1211
Cockroach 250 19/4.22 265.7 21.1 731 40.4 0.1083
Butterfly 300 19/4.65 322.7 23.25 888 48.75 0.08916
Moth 350 19/5.00 373.2 25.0 1027 56.37 0.07711
Drone 350 37/3.58 373.3 25.1 1029 57.45 0.07741
Locust 400 19/5.36 428.5 26.8 1179 64.73 0.0671
Centipede 400 37/3.78 415.5 26.46 1145 63.1 0.06944
Maybug 450 37/4.09 486.9 28.6 1342 74.01 0.05931
Scorpion 500 37/4.27 529.5 29.9 1460 79.98 0.5441
Cicada 600 37/4.65 628.6 32.6 1733 94.95 0.04588
Tarantula 750 37/5.23 794.6 36.6 2191 120.1 0.03627