Type 60227 IEC 53
FEATURES
300/500V
70℃
IEC 60227-5
APPLICATION
Ordinary PVC sheathed cord
CONSTRUCTION
Conductor
No. of conductors: 2, 3, 4 or 5
IEC 60228, class 5 conductors
Insulation
PVC compound of Type PVC/D
Assembly of cores
Circular cord: the cores and the fillers, shall be twisted together
Flat cord: the cores shall be laid parallel.
Sheath
PVC compound of type PVC/ST 5
General data for type 60227 IEC 53
| 1 | 2 | 3 | 4 | 5 | 6 | 
| Number and nominal cross-
 sectional area of conductors  | 
Thickness of insulation | Thickness of sheath
 
 Specified value  | 
Mean overall dimensions | Minimum insulation
 resistance at 70℃  | 
|
| Specified
 value  | 
Lower limit | Upper limit | |||
| mm2 | mm | mm | mm | mm | MΩ·km | 
| 2 x 0.75 | 0.6 | 0.8 | 5.7
 or 3.7 x 6.0  | 
7.2
 or 4.5 x 7.2  | 
0.011 | 
| 2 x 1 | 0.6 | 0.8 | 5.9
 or 3.9 x 6.2  | 
7.5
 or 4.7 x 7.5  | 
0.010 | 
| 2 x 1.5 | 0.7 | 0.8 | 6.8 | 8.6 | 0.010 | 
| 2 x 2.5 | 0.8 | 1.0 | 8.4 | 10.6 | 0.009 | 
| 3 x 0.75 | 0.6 | 0.8 | 6.0 | 7.6 | 0.011 | 
| 3 x 1 | 0.6 | 0.8 | 6.3 | 8.0 | 0.010 | 
| 3 x 1.5 | 0.7 | 0.9 | 7.4 | 9.4 | 0.010 | 
| 3 x 2.5 | 0.8 | 1.1 | 9.2 | 11.4 | 0.009 | 
| 4 x 0.75 | 0.6 | 0.8 | 6.6 | 8.3 | 0.011 | 
| 4 x 1 | 0.6 | 0.9 | 7.1 | 9.0 | 0.010 | 
| 4 x 1.5 | 0.7 | 1.0 | 8.4 | 10.5 | 0.010 | 
| 4 x 2.5 | 0.8 | 1.1 | 10.1 | 12.5 | 0.009 | 
| 5 x 0.75 | 0.6 | 0.9 | 7.4 | 9.3 | 0.011 | 
| 5 x 1 | 0.6 | 0.9 | 7.8 | 9.8 | 0.010 | 
| 5 x 1.5 | 0.7 | 1.1 | 9.3 | 11.6 | 0.010 | 
| 5 x 2.5 | 0.8 | 1.2 | 11.2 | 13.9 | 0.009 | 
															