AAC- All Aluminum Stranded Conductors (DIN 48201-5)
Application
It is mainly used for overhead power transmission lines.
Standards
DIN 48201-5: Aluminum Strandedd Conductors
Construction: Aluminum 1350-H19 wires, concentrically stranded
Technical Parameter
Area | Stranding and Wire Diameter | Overall Diameter | Linear Mass | Calculated Breaking Load | Maximum DC Resistance at 20℃ | |
Nominal (mm2) | Actual (mm2) | mm | mm | kg/km | KN | Ω/km |
16 | 15.89 | 7/1.71 | 5.1 | 44 | 2.9 | 1.8018 |
25 | 24.25 | 7/2.10 | 6.3 | 67 | 425.0 | 1.1808 |
35 | 34.36 | 7/2.50 | 7.5 | 94 | 5.9 | 0.8332 |
50 | 49.48 | 7/3.00 | 9.0 | 135 | 8.1 | 0.5786 |
50 | 48.36 | 19/1.80 | 9.0 | 133 | 8.6 | 0.595 |
70 | 65.82 | 19/2.10 | 10.5 | 181 | 11.5 | 0.4371 |
95 | 93.27 | 19/2.50 | 12.5 | 256 | 16.0 | 0.3084 |
120 | 117 | 19/2.80 | 14.0 | 322 | 19.1 | 0.2459 |
150 | 147.1 | 37/2.25 | 15.2 | 406 | 25.7 | 0.196 |
185 | 181.6 | 37/2.50 | 17.5 | 501 | 31.1 | 0.1587 |
240 | 242.54 | 61/2.25 | 20.2 | 670 | 40.2 | 0.1191 |
300 | 299.43 | 61/2.50 | 22.5 | 827 | 48.5 | 0.0965 |
400 | 400.14 | 61/2.89 | 26.0 | 1105 | 61.9 | 0.07221 |
500 | 499.83 | 61/3.23 | 29.1 | 1381 | 76.0 | 0.05781 |
625 | 626.2 | 91/2.96 | 32.6 | 1733 | 96.9 | 0.04625 |
800 | 802.1 | 91/3.35 | 36.8 | 2219 | 120.55 | 0.03611 |
1000 | 999.71 | 91/3.74 | 41.1 | 2766 | 148.45 | 0.02897 |