Application
The cables are suitable for direct burial and installation in ducts.
Temperature rating
Conductor Maximum Continuous Temperature:90°C
Emergency Temperature:130°C
Ambient Temperature: -25 to 40°C
Installation & Handling Temperature: -25 to 40°C
Voltage rating: 25KV
Standards and Approval
CSA C68.10-14 – Shielded power cable for commercial and industrial applications, 5–46 kV
FT-4: Smoke and flame propagation as per ANSI/UL1685 flame propagation as per NFPA 262
NFPA 130: Fire Resistant and low smoke emissions
ICEA S-93-639: 5-46 kV Shielded Power Cable for Use in the Transmission and Distribution of Electric Energy
CSA approved
Construction
Conductor: Class B compact bare copper strand
Conductor Shield: Extruded semi-conducting thermoset compound
Insulation (133% level): Tree-Retardant cross-linked Polyethylene (TR-XLPE)
Insulation Shield: Extruded semi-conducting thermoset compound
Metalic Shield: Overlapping copper tape shield
Jacket: 90°C flame-resistant low smoke sunlight resistant PVC
Technical Parameter
Size | No. of Copper Wires | OD of Compact Conductor | Conductor Shield Thickness | TR-XLPE Insulation Thickness | Insulation Shield Thickness | Copper Tape Shield Thickness | PVC Jacket Thickness | Approx. Overall Diameter | Approx. Cable Weight |
AWG or Kcmil | mm | mm | mm | mm | mm | mm | mm | lbs/1000ft | |
2/0 | 19 | 9.55 | 0.8 | 8.13 | 0.8 | 0.12 | 2.03 | 33.4 | 1055 |
3/0 | 19 | 10.74 | 0.8 | 8.13 | 0.8 | 0.12 | 2.03 | 34.6 | 1193 |
4/0 | 19 | 12.07 | 0.8 | 8.13 | 0.8 | 0.12 | 2.03 | 35.9 | 1366 |
250 | 37 | 13.21 | 0.8 | 8.13 | 0.8 | 0.12 | 2.03 | 37.0 | 1509 |
350 | 37 | 15.65 | 0.8 | 8.13 | 0.8 | 0.12 | 2.03 | 39.5 | 1885 |
500 | 37 | 18.7 | 0.8 | 8.13 | 0.8 | 0.12 | 2.79 | 44.0 | 2525 |
750 | 60 | 23.06 | 0.8 | 8.13 | 0.8 | 0.12 | 2.79 | 48.4 | 3416 |
1000 | 60 | 26.92 | 0.8 | 8.13 | 0.8 | 0.12 | 2.79 | 52.2 | 4289 |