Jiangsu Ganghong Electric Wire and Power Cable Corporation Limited

ACS- Aluminum-Clad Steel Conductor

Application
It is widely used for electric transmission line conductors.

Standards
IEC61089 – Round Wire Concentric Lay Overhead Electrical Stranded Conductors

Construction: Made from a number of round  aluminum-clad steel wires as per IEC61632

Technical Parameter for ACS (SA1A, SA1B)

Nom. St                    Area Code Number Area No.of Wires Diameter Linear Mass Rated Strength Max. DC Resistance  at 20 ℃
Wire Cond. SA1A or JLB1A SA1B or JLB1B SA1A or JLB1A SA1B or JLB1B
    mm2 mm2 mm mm kg/km kg/km   kN   kN Ω/km
15 4 12 7 1.48 4.43 80.1 79.4 16.08 15.84 7.1592
20 6.3 18.9 7 1.85 5.56 126.2 125 25.33 24.95 4.5455
30 10 30 7 2.34 7.01 200.3 198.5 40.2 39.6 2.8637
35 12.5 37.5 7 2.61 7.84 250.4 248.1 50.25 49.5 2.291
50 16 48 7 2.95 8.86 320.5 317.5 64.32 63.36 1.7898
75 25 75 7 3.69 11.08 500.7 496.2 93.75 99.0 1.1455
120 40 120 7 4.67 14.02 801.2 793.9 132 158.4 0.7159
120 40 120 19 2.84 14.18 805 797.7 160.8 158.4 0.7194
200 63 189 19 3.56 17.79 1267.9 1256.4 240.03 249.4 0.4568
300 100 300 37 3.21 22.49 2017.3 1999 402 396 0.2884
350 125 375 37 3.59 25.15 2521.7 2498.3 476.25 495 0.2307
450 150 480 37 4.06 28.45 3227.7 3198.3 580.8 633.6 0.1803
600 200 600 37 4.54 31.81 4034.7 3997.9 684 792 0.1442
600 200 600 61 3.54 31.85 4040.6 4003.8 762 792 0.1444

Technical Parameter for ACS (SA2)

Nom. St Area Code Number Area No.of wires Diameter Linear Mass Rated Strength Max. DC Resistance at 20 ℃
Wire Cond.
mm2 mm2 mm mm kg/km  kN Ω/km
35 16 36.2 7 2.56 7.69 216.4 39.04 1.7896
55 25 56.5 7 3.21 9.62 338.2 61.0 1.1454
100 40 90.4 7 4.05 12.2 541.7 97.61 0.7159
100 40 90.4 19 2.46 12.3 543.7 97.61 0.7193
150 63 142 19 3.09 15.4 856.4 153.73 0.4567
220 100 226 37 2.79 19.5 1362.6 244.02 0.2884
300 125 282 37 3.12 21.8 1703.2 305.02 0.2307
350 160 362 37 3.53 24.7 2180.1 390.43 0.1803
450 200 452 37 3.94 27.6 2725.1 488.03 0.1442
450 200 452 61 3.07 27.6 2729.1 488.03 0.1444