Application
Type SJ flexible cords are used for applications that require extra hard usage, portable lights, battery charges,
portable stage lights, heavy tools and other industrial equipment.
Temperature rating and voltage rating
60°C / 75°C / 90°C / 105°C and 300V
Standards and approval
UL62 – Flexible Cords and Cables
CSA 22.2 No. 49 – Flexible Cords and Cables
UL & CSA listed, UL File No. E518108
Construction
Conductor: Bare or tinned soft copper conductor
Separator: Polyester tape
Insulation: Rubber
Core identification
2 cores: black,white
3 cores:black, white, green
4 cores:black, white, green, red
Binder:Semi-conductive wrap tape with filler if necessary
Jacket: Rubber
Technical Parameter
Size | Conductor Stranding | Insulation Thickness | Jacket Thickness | Approx. Overall Diameter | Approx. Net Weight | ||||
mm | mils | mm | mils | mm | inch | kg/km | lbs/1000ft | ||
2X18AWG | 16X30 | 0.76 | 30 | 0.76 | 30 | 7.4 | 0.291 | 73 | 49 |
3X18AWG | 16X30 | 0.76 | 30 | 0.76 | 30 | 7.9 | 0.310 | 95 | 64 |
4X18AWG | 16X30 | 0.76 | 30 | 0.76 | 30 | 8.6 | 0.340 | 110 | 74 |
2X16AWG | 26X30 | 0.76 | 30 | 0.76 | 30 | 7.9 | 0.312 | 89 | 60 |
3X16AWG | 26X30 | 0.76 | 30 | 0.76 | 30 | 8.4 | 0.331 | 116 | 78 |
4X16AWG | 26X30 | 0.76 | 30 | 0.76 | 30 | 9.3 | 0.367 | 146 | 98 |
2X14AWG | 41X30 | 0.76 | 30 | 0.76 | 30 | 8.7 | 0.344 | 112 | 75 |
3X14AWG | 41X30 | 0.76 | 30 | 0.76 | 30 | 9.4 | 0.370 | 147 | 99 |
4x14AWG | 41X30 | 0.76 | 30 | 0.76 | 30 | 10.4 | 0.410 | 183 | 123 |
2X12AWG | 65X30 | 0.76 | 30 | 1.14 | 45 | 10.8 | 0.425 | 171 | 115 |
3X12AWG | 65X30 | 0.76 | 30 | 1.14 | 45 | 11.3 | 0.445 | 205 | 138 |
4x12AWG | 65X30 | 0.76 | 30 | 1.14 | 45 | 12.3 | 0.485 | 275 | 185 |
2X10AWG | 104X30 | 1.14 | 45 | 1.52 | 60 | 14.5 | 0.572 | 298 | 200 |
3X10AWG | 104X30 | 1.14 | 45 | 1.52 | 60 | 15.3 | 0.601 | 363 | 244 |
4x10AWG | 104X30 | 1.14 | 45 | 1.52 | 60 | 16.8 | 0.660 | 455 | 306 |