Jiangsu Ganghong Electric Wire and Power Cable Corporation Limited

,

H05Z-K / H07Z-K

H05Z-K / H07Z-K

300/500V for H05Z-K , 450/750V for H07Z-K, 90º C

Single core non-sheathed cable with flexible conductors for general purposee

Application
These cables are designed for the internal wiring of switchboards and distributor boards with an alternating nominal voltage up to 1000 Volts or a direct voltage up to 750 volts.
Standard
HD 22.9 S2, VDE-0282 Part-9, BS 7211, IEC 60754-2, EN 50267, VDE 0482-267
Construction
Conductor: Fine bare copper strands, according to EN 60228 Class 5, IEC 60228 Class 5
Insulation: LSOH cross-link polyolefin
Technical Characteristics
Rated voltage: 300/500V (H05Z-K), 450/750V (H07Z-K)
Test voltage: 2500V
Flexing bending radius: 8 x Ø
Static bending radius: 8 x Ø
Operating temperature: -15º C to +90º C
Smoke density acc. to EN 50268 / IEC 61034
Corrosiveness of combustion gases acc. to EN 50267-2-2, IEC 60754-2
Flame test: flame-retardant acc. to EN 50265-2-1, IEC 60332.1

Technical Parameter

Nominal Cross Sectional Area No. of wires Wire Dia. Nom.  PVC Insulation Thickness Overall Diameter Min. Insulation Resistance  at  90°C Maximum  Resistance of Conductor at 20°C
Min. OD Max. OD Plain Copper Wires
 mm² mm mm mm mm Mohm.km Ω/km
H05Z-K
0.5 16 0.2 0.6 2.1 2.6 0.013 39.0
0.75 24 0.2 0.6 2.2 2.8 0.011 26.0
1 32 0.2 0.6 2.4 2.9 0.010 19.5
H07Z-K
1.5 30 0.25 0.7 2.8 3.5 0.010 13.3
2.5 50 0.25 0.8 3.4 4.3 0.009 7.98
4 56 0.3 0.8 3.9 4.9 0.007 4.95
6 84 0.3 0.8 4.4 5.5 0.006 3.30
10 80 0.4 1.0 5.7 7.1 0.0056 1.91
16 128 0.4 1.0 6.7 8.4 0.0046 1.21
25 200 0.4 1.2 8.4 10.6 0.0044 0.780
35 280 0.4 1.2 9.7 12.1 0.0038 0.554
50 400 0.4 1.4 11.5 14.4 0.0037 0.386
70 356 0.5 1.4 13.2 16.6 0.0032 0.272
95 485 0.5 1.6 15.1 18.8 0.0032 0.206
120 614 0.5 1.6 16.7 20.9 0.0029 0.161
150 765 0.5 1.8 18.6 23.3 0.0029 0.129
185 944 0.5 2.0 20.6 25.8 0.0029 0.106
240 1225 0.5 2.2 23.5 29.4 0.0028 0.0801

 

Scroll to Top